976
Serial Communications Instructions
Section 3-24
Description
PMCR(260) will execute the communications sequence specified in C2 using
the logical port specified in bits 12 to 15 of C1 and the physical port specified
in bits 8 to 11 of C1 for the unit address specified in bits 0 to 7 of C1.
If a symbol is specified as the operand for a send message, the number of
send words specified in S and beginning from S+1 will be used as the send
area. If a symbol is specified as the operand for a receive message, receive
data is placed in memory staring with R+1 and the number of words received
is automatically written to R if the transmission is successful.
If the transmission fails, the data (R+1 onward) set before PMCR(260) was
executed will be read from the receive buffer and stored in the R+1 onward
again.
Flags
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
Specified
values only
0000 to
03E7Hex
(0 to 999)
#0000 (binary)
Data Registers
DR0 to DR15
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area
C1
C2
S
R
R
to
to
CPU Unit
External
device
Serial Communications Unit
Port
Name
Label
Operation
Error Flag
ER
ON if the Communications Port Enabled Flag is OFF for
the specified logical port when PMCR(260) is executed.
ON if C1 is not within the specified ranges. (Error flag will
not turn ON if the C2 data is outside the specified ranges.
The end code will be stored in the Communications Port
Completion Code (A203 to A210) of the auxiliary area.)
ON if the number of words of S or R exceeds 249 (when
words are specified).
OFF in all other cases.
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...