1176
Other Instructions
Section 3-31
Note If there is no CS/CJ-series equivalent to the specified CV-series PLC memory
address, an error will occur, the Error Flag will be turned ON, and the address
will not be converted.
When an Index Register is used as an operand with a “,IR” prefix, the instruc-
tion will operate on the word indicated by the PLC memory address in the
Index Register, not the Index Register itself. Once the desired PLC memory
address has been stored in an Index Register, the Index Register itself can be
used as an operand for an instruction.
The FRMCV(284) instruction can be used to convert a CV-series program
with the following two kinds of programming for use in a CS/CJ-series PLC.
See the Examples later in this section for an example.
1.
When using indirect binary mode DM addressing (
*
DM)
(when indirectly specifying a data area address with a PLC memory ad-
dress in DM)
2.
When using CV-series PLC memory addresses directly as values
(when storing PLC memory addresses in Index Registers with direct ad-
dressing using an instruction such as MOV(021))
Operand Specifications
0000Hex
0001Hex
2000Hex
2001Hex
FFFDHex
0000CH
0001CH
D00000
D00001
E32765
0C000Hex
0C001Hex
10000Hex
10001Hex
FFFFFHex
0000CH
0001CH
D00000
D00001
EC_32767
S
IR1
10001Hex
D:
Specify the CV-series PLC
memory address in S. (In this
case, 2001 hex is the PLC
memory address of D00001.)
Data area address
PLC memory address
Convert
Corresponding
data area
address
CV-series
The corresponding CS/CJ-series PLC
memory address is stored in D. (In this
case, data area address D00001 is
converted to PLC memory address
10001 hex and stored.)
Convert
CS/CJ-series
Area
S
D
CIO Area
CIO 0000 to CIO 6143
---
Work Area
W000 to W511
---
Holding Bit Area
H000 to H511
---
Auxiliary Bit Area
A448 to A959
---
Timer Area
T0000 to T4095
---
Counter Area
C0000 to C4095
---
DM Area
D00000 to D32767
---
EM Area without bank
E00000 to E32767
---
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
---
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...