Symbol Math Instructions
Section 3-11
Description
*BL(425) multiplies BCD values in Md and Md+1 and Mr and Mr+1 and out-
puts the result to R, R+1, R+2, and R+3.
Flags
Precautions
If Md, Md+1 and/or Mr, Mr+1 are not BCD, an error will be generated and the
Error Flag will turn ON.
If as a result of the multiplication, the content of R, R+1, R+2, R+3 is
00000000 hex, the Equals Flag will turn ON.
Examples
When CIO 000000 is ON in the following example, D00101, D00100, D00111,
and D00110 will be multiplied as 8-digit unsigned BCD values and the result
will be output to D00123, D00122, D00121 and D00120.
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
#00000000 to #99999999
(BCD)
---
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area
Md
Mr
R
R + 1
R
R + 3
R + 2
(BCD)
(BCD)
(BCD)
×
Md + 1
Md
Mr + 1
Mr
Name
Label
Operation
Error Flag
ER
ON when Md and/or Md+1 are not BCD.
ON when Mr and/or Mr +1 are not BCD.
OFF in all other cases.
Equals Flag
=
ON when the result is 0.
OFF in all other cases.
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...