501
Troubleshooting
Section 12-5
12-5 Troubleshooting
This section provides troubleshooting flowcharts when Servo Drive communi-
cations cannot be established or movement is not possible even when move-
ment commands are sent from the ladder program.
12-5-1 Initial Troubleshooting
The following troubleshooting flowchart is for errors that occur during initial
checking.
This flowchart can be used to determine whether the PCU is faulty and cannot
be started.
N
Y
Y
N
Y
N
Y
N
Y
Y
N
N
The Servo Drive cannot communicate.
The Servomotor will not operate in
response to commands.
Is the RUN indicator lit?
Are any other
indicators lit?
Is the ERH indicator lit?
Is power being supplied to
the PLC correctly?
Is the unit number
set correctly?
Are the I/O tables
set correctly?
Supply the correct
power supply
voltage to the PLC.
Make sure that the PCU
is installed correctly,
and turn the power OFF
and ON again.
If the problem occurs
again, the probable
cause is a faulty PCU
Unit. Replace the PCU.
Create the I/O
tables for the CPU
Unit again.
Check whether the
PCU's unit number is
the same as another
Unit.
See
12-5-2
Troubleshooting
during PCU
Operations
.
Summary of Contents for CJ1W-NC271 - 12-2009
Page 2: ......
Page 4: ...iv ...
Page 6: ...vi ...
Page 22: ...xxii ...
Page 58: ...30 Starting Operation Section 2 2 ...
Page 244: ...216 Axis Operating Input Memory Areas Section 4 8 ...
Page 264: ...236 Transferring Servo Parameters Section 5 3 ...
Page 396: ...368 Linear Interpolation Section 9 7 ...
Page 648: ...620 List of Error Codes Appendix D ...
Page 674: ...646 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Page 684: ...656 Index ...
Page 686: ...658 Revision History ...