70
Wiring
Section 3-4
Note
(1) When using crimp terminals, use crimp terminals with the following di-
mensions.
(2) When connecting wires and crimp terminals to a terminal block, tighten
them with a tightening torque of 0.59 N·m.
XW2D-20G6
The XW2D-20G6 is an M3 Screw Terminal Block.
Dimensions
Note
(1) When using crimp terminals, use crimp terminals with the following di-
mensions.
Applicable Crimp Terminals
Applicable Wires
Round Crimp
Terminals
1.25-3
AWG22-16
(0.3 to 1.25 mm
2
)
2-3.5
AWG16-14
(1.25 to 2.0 mm
2
)
Fork Terminals
1.25Y-3
AWG22-16
(0.3 to 1.25 mm
2
)
2-3.5
AWG16-14
(1.25 to 2.0 mm
2
)
6.8 mm max.
3.7 mm
6.8 mm max.
3.2-mm dia.
Round Crimp Terminals
Fork Terminals
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10
B1 B2 B3 B4 B5 B 6 B7 B
8 B9
B10
79
57
Two, 4.5-dia.
(39.1)
17.6
39
6
40
(4.5)