177
Servo Parameter Area
Section 4-5
■
Control Function Parameters
Param-
eter No.
Parame-
ter name
Param-
eter
size
Contents
Default
setting
Unit
Setting range
Enable
setting
Details
Digit
No.
Name
Set-
ting
Explanation
Pn800
Commu-
nications
control
2
0
Not used.
0
(Do not
change the
setting.)
1
---
---
---
---
1
Warning
check mask
0
Detects
parameter
setting warn-
ings (A.94),
command
warnings
(A.95), and
communica-
tions errors
(A.96).
4
---
---
Online
Always set
to 4 or 0.
1
Ignores
parameters
setting warn-
ings (A.94).
2
Ignores com-
mand warn-
ings (A.95).
3
Ignores both
parameter
setting warn-
ings (A.94)
and com-
mand warn-
ings (A.95).
4
Ignores com-
munications
errors (A.96).
5
Ignores both
parameter
setting warn-
ings (A.94)
and commu-
nications
errors (A.96).
6
Ignores both
command
warnings
(A.95) and
communica-
tions errors
(A.96).
7
Ignores
parameter
setting warn-
ings (A.94),
command
warnings
(A.95), and
communica-
tions errors
(A.96).
2
Not used.
0
(Do not
change the
setting.)
0
---
---
---
---
3
Not used.
0
(Do not
change the
setting.)
0
---
---
---
---
Summary of Contents for CJ1W-NC271 - 12-2009
Page 2: ......
Page 4: ...iv ...
Page 6: ...vi ...
Page 22: ...xxii ...
Page 58: ...30 Starting Operation Section 2 2 ...
Page 244: ...216 Axis Operating Input Memory Areas Section 4 8 ...
Page 264: ...236 Transferring Servo Parameters Section 5 3 ...
Page 396: ...368 Linear Interpolation Section 9 7 ...
Page 648: ...620 List of Error Codes Appendix D ...
Page 674: ...646 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Page 684: ...656 Index ...
Page 686: ...658 Revision History ...