74
Wiring
Section 3-4
Note
Connect surge-suppressing diodes or surge suppressors close to relays. Use
surge-suppressing diodes with a dielectric strength of at least 5 times the cir-
cuit voltage.
• Noise may be transferred through the power line if there is nearby equip-
ment that generates high-frequency noise or the power supply is shared
with equipment such as an electric welder or electric discharge equip-
ment. In this case, insert a noise filter in the power supply input line.
• Connect to a ground of 100
Ω
or less and use the thickest possible wire,
greater than 1.25 mm
2
.
• Twisted-pair cable is recommended for power lines.