![background image](http://html1.mh-extra.com/html/omron/cj1w-nc271-12-2009/cj1w-nc271-12-2009_operation-manual_742348269.webp)
241
MECHATROLINK Settings
Section 6-2
6-2-2
Scan List and PCU Area Allocations
Words are allocated to the PCU in the Work Area in the CPU Unit for use as
Axis Operating Output Memory Areas and Axis Operating Input Memory
Areas for the Servo Drives registered in the scan list. An output area of 25
words and an input area of 25 words are allocated to each axis according to
the axis number registered in the scan list. The beginning word of these out-
put areas and input areas can be set by the user in the Common Parameter
Area.
The output areas and input area allocations are specified in the four words of
data in the PCU's internal addresses from 1838 to 183B hex, as shown in the
following table. The Common Parameters settings saved in the PCU's internal
flash memory are enabled when the PCU power is turned ON or the Unit is
restarted.
The Axis Operating Memory Output and Input Areas are allocated words for
each axis from axis 1 up to the highest axis number registered in the scan list.
Axis numbers between axis 1 and the highest registered axis number that are
not registered as MECHATROLINK devices are also each allocated 25 output
words and 25 input words.
PCU's
address
Contents
Setting
1838 hex
Axis Operating Out-
put Memory Area
designation
Specifies the words allocated for the Axis Oper-
ating Output Memory Areas.
0000 hex: No setting (default)
00B0 hex: CIO Area
00B1 hex: Work Area
00B2 hex: Holding Area
00B3 hex: Auxiliary Area
0082 hex: DM Area
0050 to 0059, 005A,005B, 005C hex:
EM Area (5
@
:
@
= EM Bank No.)
1839 hex
Beginning word of
Axis Operating Out-
put Memory Areas
Specifies the beginning word of the Axis Operat-
ing Output Memory Areas. The beginning word
of the Operating Output Memory Area for axis 1
is determined by the Axis Operating Output
Memory Area designation and the word deter-
mined using this parameter. Each axis is allo-
cated 25 words in sequence from this word.
183A hex
Axis Operating Input
Memory Area desig-
nation
Specifies the words allocated for the Axis Oper-
ating Input Memory Areas. The setting method
is the same as for the Axis Operating Output
Memory Areas.
183B hex
Beginning word of
Axis Operating Input
Memory Areas
Specifies the beginning word of the Axis Operat-
ing Input Memory Areas. The setting method is
the same as for the Axis Operating Output Mem-
ory Areas.
Summary of Contents for CJ1W-NC271 - 12-2009
Page 2: ......
Page 4: ...iv ...
Page 6: ...vi ...
Page 22: ...xxii ...
Page 58: ...30 Starting Operation Section 2 2 ...
Page 244: ...216 Axis Operating Input Memory Areas Section 4 8 ...
Page 264: ...236 Transferring Servo Parameters Section 5 3 ...
Page 396: ...368 Linear Interpolation Section 9 7 ...
Page 648: ...620 List of Error Codes Appendix D ...
Page 674: ...646 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Page 684: ...656 Index ...
Page 686: ...658 Revision History ...