Reading Servo
Parameters
Use the READ SERVO PARAMETER Bit in the Axis Operating Output Mem-
ory Area to read the Servo Parameters from the Servo Drive to the CPU Unit's
DM Area.
When the Servo Parameter transfer operation's execution condition goes ON,
the Servo Parameter (specified in the DM Area as shown below) will be read.
When the Servo Parameter data has been read normally, W401.05 is turned
ON for one cycle and the parameter is stored in the DM Area as shown in the
following table.
When the read operation was not completed normally, i.e., an error occurred
during the transfer, W401.06 will be turned ON for one cycle. (There must be
no axis error before execution of this sample program.)
Word
Details
D10500
Servo Parameter No.
D10501
Parameter size (Unit: bytes)
Word
Details
D10502
Read data (rightmost)
D10503
Read data (leftmost)