Part 2: Review on Replacement of MR-J3-_A_ with MR-J4-_A_
2 - 46
MR-J3-_A_
MR-J4-_A_
Control
mode
No.
Name and function
Initial
value
No.
Name and function
Initial
value
PC20 Station number setting
Used to specify the station number for serial
communication.
Always set one station to one axis of servo amplifier.
If one station number is set to two or more stations,
normal communication cannot be made.
0 PC20
Same setting as MR-J3
0 P
S
T
Station No. setting
Specify a station number of the servo amplifier for
RS-422/RS-485 and USB communications.
Always set one station to one axis of the servo
amplifier. Setting one station number to two or more
stations will disable a normal communication.
Setting range: 0 to 31
PC21
Communication function selection
Select the communication I/F and select the RS-422
communication conditions.
0 0 x 0:
RS-422 communication baud rate selection
0: 9600 [bps]
1: 19200 [bps]
2: 38400 [bps]
3: 57600 [bps]
4: 115200 [bps]
0000h PC21
RS-422 communication function selection
Select the communication I/F and select the RS-422
communication conditions.
_ _ _ x:
For manufacturer setting
0h
_ _ x _:
RS-422 communication baud rate selection
When using the parameter unit, set "1 _ _ _" in [Pr.
PF34].
0: 9600 [bps]
1: 19200 [bps]
2: 38400 [bps]
3: 57600 [bps]
4: 115200 [bps]
0h P
S
T
0 x 0 0:
RS-422 communication response delay time
0: Invalid
1: Valid, reply sent after delay time of 800
μ
s or
longer
_ x _ _:
RS-422/RS-485 communication response delay time
selection
0: Disabled
1: Enabled (responding after 800
μ
s or longer delay
time)
0h P
S
T
x _ _ _:
For manufacturer setting
0h
PC22
Function selection C-1
Select the execution of automatic restart after
instantaneous power failure selection, and encoder
cable communication system selection.
0 0 0 x:
Restart after instantaneous power failure selection
If the power supply voltage has returned to normal
after an undervoltage status caused by the
reduction of the input power supply voltage in the
speed control mode, the servo motor can be
restarted by merely turning on the start signal
without resetting the alarm.
0: Invalid ([AL.10 Undervoltage alarm ] occurs.)
1: Valid
0000h PC22
_ _ _ x:
For manufacturer setting
0h
_ _ x _:
For manufacturer setting
0h
_ x _ _:
For manufacturer setting
0h
Function selection C-1
x _ _ _:
Encoder cable communication method selection
Select how to execute the encoder cable
communication method.
0: Two-wire type
1: Four-wire type
When using an encoder of A/B/Z-phase differential
output method, set "0".
If the setting is incorrect, [AL. 16 Encoder initial
communication error 1] or [AL. 20 Encoder normal
communication error 1] occurs.
0h P
S
T
x 0 0 0:
Encoder cable communication system
selection
0: Two-wire type
1: Four-wire type
The following encoder cables are four-wire type.
MR-EKCBL30M-L
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
Other encoder cables are two-wire type.
Incorrect setting will result in an encoder error
1 (At power ON) (AL.16).
Summary of Contents for Melservo MR-J3-100B
Page 17: ...8 MEMO ...
Page 18: ...Part 1 Summary of MR J3 MR J3W Replacement 1 1 Part 1 Summary of MR J3 MR J3W Replacement ...
Page 145: ...Part 3 Review on Replacement of MR J3 _B_ with MR J4 _B_ 3 48 MEMO ...
Page 195: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 50 MEMO ...
Page 277: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 82 MEMO ...
Page 278: ...Part 6 Common Reference Material 6 1 Part 6 Common Reference Material ...
Page 418: ...Part 7 Review on Replacement of Motor 7 1 Part 7 Review on Replacement of Motor ...
Page 564: ...Part 9 Startup Procedure Manual 9 1 Part 9 Startup Procedure Manual ...
Page 567: ...Part 9 Startup Procedure Manual 9 4 MEMO ...
Page 589: ...L NA 03127ENG C ...