Part 5: Review on Replacement of MR-J3-DU_ with MR-J4-DU_
5 - 46
6.2 Power supply capacity and generated loss
(1) Generated heat of the converter unit/drive unit
Table 5.1 and 5.2 indicates the generated loss and power supply capacity under rated load per
combination of the resistance regeneration converter unit and drive unit. When the servo motors are run
at less than the rated speed, the power supply equipment capacity is lower than the value in the table
but the heat generated does not change.
Since the servo motor requires 2 times to 2.5 times greater instantaneous power for acceleration, use
the power supply which ensures that the voltage lies within the permissible voltage fluctuation at the
main circuit power supply terminals (L1/L2/L3) of the resistance regeneration converter unit. The power
supply equipment capacity changes with the power supply impedance. The actually generated heat falls
within the ranges at rated output and at servo-off according to the frequencies of use during operation.
When designing an enclosed cabinet, use the values in the table, considering the worst operating
conditions. The generated heat in table 5.1 and 5.2 does not include heat produced during regeneration.
(a) MR-J3-DU_
Table 5.1 Power supply capacity and generated heat per servo amplifier at rated output
Converter unit
Drive unit
Servo motor
Power supply capacity [kVA]
Drive unit-generated heart [W] (Note)
Area
required
for heat
dissipation
[m
2
]
Power factor
improving DC
reactor is not
used
Power factor
improving DC
reactor is
used
At rated torque
At rated output
[Generated heat
in the cabinet
when cooled
outside the
cabinet]
At zero torque
MR-J3-CR55K
MR-J3-DU30KB
HA-LP30K1
HA-LP30K1M
HA-LP30K2
48
40
1550 (1100 + 450)
470
31.0
MR-J3-DU37KB
HA-LP37K1
HA-LP37K1M
HA-LP37K2
59
49
1830 (1280 + 550)
550
36.6
MR-J3-DU30KB4
HA-LP25K14
40
35
1080 (850 + 230)
330
21.6
HA-LP30K14
HA-LP30K1M4
HA-LP30K24
48
40
1290 (1010 + 280)
390
60 (30 + 30)
25.8
MR-J3-CR55K4 MR-J3-DU37KB4
HA-LP37K14
HA-LP37K1M4
HA-LP37K24
59
49
1542 (1200 + 342)
470
30.8
MR-J3-DU45KB4
HA-LP45K1M4
HA-LP45K24
71
59
1810 (1370 + 440)
550
36.2
MR-J3-DU55KB4
HA-LP50K1M4
80
67
2120 (1650 + 470)
640
42.4
HA-LP55K24
87
72
2150 (1650 + 500)
650
43.0
Note. The heat generated by the drive unit is indicated in the left term within the parentheses, and the heat generated by the converter
unit in the right term.
Summary of Contents for Melservo MR-J3-100B
Page 17: ...8 MEMO ...
Page 18: ...Part 1 Summary of MR J3 MR J3W Replacement 1 1 Part 1 Summary of MR J3 MR J3W Replacement ...
Page 145: ...Part 3 Review on Replacement of MR J3 _B_ with MR J4 _B_ 3 48 MEMO ...
Page 195: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 50 MEMO ...
Page 277: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 82 MEMO ...
Page 278: ...Part 6 Common Reference Material 6 1 Part 6 Common Reference Material ...
Page 418: ...Part 7 Review on Replacement of Motor 7 1 Part 7 Review on Replacement of Motor ...
Page 564: ...Part 9 Startup Procedure Manual 9 1 Part 9 Startup Procedure Manual ...
Page 567: ...Part 9 Startup Procedure Manual 9 4 MEMO ...
Page 589: ...L NA 03127ENG C ...