259
Software Limit
Section 9-9
The relationship between the CW and CCW limit input signals, the software
limits, and the mechanical stoppers used in the system, is shown below.
The software limit function is enabled if an origin has been established (i.e.,
the No Origin Flag is OFF) and the CW software limit setting is greater than
the CCW software limit setting. In any other situation, the software limit func-
tion will be disabled and operation for the present position will proceed as fol-
lows.
• From the stopped state, before pulse output is started, the present posi-
tion is set to 0.
• During pulse output, the present position will be changed as long as the
position does not go outside the following upper and lower limits:
For pulse output in CW direction: 2,147,483,647 pulses (7FFFFFFF Hex)
For pulse output in CCW direction: –2,147,483,647 pulses (80000001
Hex)
9-9-2
Beginning Words of Memory Areas
The beginning words of the operating memory area, operating data area, and
common parameter area used for a Position Control Unit (PCU) are deter-
mined (or set) according to the following.
• Beginning word of the operating memory area, n = CIO 2000 + 10
×
unit
number
• Beginning word of the common parameter area, m = 100
×
unit
number
• Beginning word of the operating data area, l, is specified in m and m+1.
Set the beginning words of the operating data area and designate the axis
parameters used with the common parameters as shown below.
CCW software limit
CW software limit
Software level operating range
CCW limit signal input
CW limit signal input
Electrical level operating range
Mechanical stopper
Mechanical level operating range
Mechanical stopper
Word
Name
Bit
Reference
m
Operating data area designation
00 to 15
SECTION 4
m+1
Beginning word of operating data area
00 to 15
m+2
Axis parameter designation
00 to 15
Содержание CJ1W-C113 - REV 02-2008
Страница 1: ...Position Control Units Cat No W397 E1 07 SYSMAC CJ1W NC113 213 413 133 233 433 OPERATION MANUAL ...
Страница 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Страница 3: ...iv ...
Страница 13: ...xiv ...
Страница 15: ...xvi ...
Страница 19: ...xx ...
Страница 27: ...xxviii Conformance to EC Directives 6 ...
Страница 43: ...16 Control System Principles Section 1 7 ...
Страница 47: ...20 Basic Procedures Section 2 ...
Страница 139: ...112 Examples of Parameter Settings Section 4 9 ...
Страница 173: ...146 Transferring Data with CX Position Section 5 7 ...
Страница 223: ...196 Sample Program Section 7 7 ...
Страница 259: ...232 Sample Program Section 8 10 ...
Страница 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Страница 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Страница 385: ...358 Common Parameter Area Appendix C ...
Страница 399: ...372 Parameter Coding Sheets Appendix E ...