Chapter 4 - Electrical Connections
_______________________________________________________________________________________________________________
MNL000298.doc
Revision 2
09/16/2016
SourceSystem TE11
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
4
-
5
Figure 4.3: Power Supply Terminal Connector
The power requirements are as follows:
100-240 VAC @ 150 VA maximum.
Overvoltage protection:
Recommended; may be required be local code
Sizing:
25% (minimum) over required load (add all cabinet loads
and divide by 0.75)
NOTE:
Power wiring must be sized to deliver the required voltage at the
rated current. Voltages should be checked at each cabinet after installation
to ensure proper levels.