Chapter 8 - Operating Procedures
___________________________________________________________________________________________________________
MNL000302.doc
Revision 2
01/04/2019
SourceSystemTE11
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
8
-
23
Before proceeding further, verify that
process equipment and facility piping is
ready to receive process gas.
20.
When the controller status box indicates “—POST PURGE COMPLETE—“, select “—
START
PROCESS GAS—“.
21.
Adjust the process gas regulator, through the access window, to the desired delivery pressure.
22.
Process gas is now flowing to the process equipment.
8.5
Manual Mode Operation
Only experienced operators should operate
the cabinet in manual mode. Operating
valves out of their proper sequence could
potentially cause damage to the product by
interrupting or providing insufficient gas
flow. Manual operation should not be
used for normal, daily operation.
NOTE: Opening high pressure vent valves when high pressure gas is present
could cause damage to the vent line pressure transducer, if installed.
Manual mode provides a means of flowing purge gas through the purge and process gas panels
during cabinet installation and pre-start-up procedures. It also provides a means of flowing purge
gas while maintenance or repairs are being performed.
8.5.1 How to Operate in Manual Mode