4.3
Field Connections
In NEC Class 1, Division 2 areas (only in the
U.S.A.), a conduit seal (“pour fitting”) or
equivalent must be installed between each
electrical connection point on the cabinet and
the electrical source. Liquid tight flexible
conduit can be installed between the
GASGUARD® TE11 connectors and the
conduit seals to facilitate these connections. A
maximum length of 18” (457 mm) is allowed
between the last pour fitting and the cabinet
connector. All conduits shall be sealed in
accordance to Sections 501-5, 502-5 or 504-70
of the National Electric Code. See Figures 4.4
and 4.5 for details.
In classified hazardous areas – Do not separate
electrical terminations or connectors while
energized due to the risk of electrical arc or
spark which can ignite potentially flammable
atmospheres.