Chapter 5 - Helium Leak Testing
_______________________________________________________________________________________________________________
MNL000299.doc
Revision 1
09/16/2016
SourceSystem TE11
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
5
-
4
1.
Enter second level (or higher) security code (check with appropriate Versum Materials, Inc.
representative for proper password as follows:
Press touch screen.
The LCD screen will prompt: “PASSWORD”
Type in the password.
Press “OK”
It the password is correct, the Main Menu will be displayed. If the password is
incorrect, “**The password window will display “BLUE” color and Invalid Password at
bottom of window **” will be displayed.
2.
From the Mode Menu screen, highlight “MANUAL MODE” by pressing Manual Mode button
(if the button is red and displays N/A a shutdown has occurred that prevents manual operation)
2.1
A legend, located on the graphics panel indicates:
TE11 Color controller:
Green – valve closed (Default)
Red - valve open (Default)
3.
Follow the procedures below to open and close valves. (Valves that can be controlled manually
are shown highlighted with a square box around them).
To open a valve:
3.1
Select the valve by touching the screen.
3.2
The valve state menu will appear asking you to confirm that you want to open the
Valve by pressing “Open Valve”. Pressing “Secure Mode” will close the menu leaving
the valve closed.
To close a valve:
3.3
Touch the valve you wish to close.
3.4
The valve state will toggle from open to close.