background image

1

Summary of Contents for KT10X

Page 1: ...1 ...

Page 2: ... professional technician It is strongly advised to place a protective guard around the unit to keep children away from the heat pump An authorized electrician must connect the Heat Pump to the power 230V 1ph or 400V 3ph Remarks Make sure that you have enough power See page 15 Cable table 380 400V 3ph 50Hz 230V 1ph 50Hz WATER PUMP POWER SUPPLY POWER SUPPLY WATER PUMP See diagram above for minimum d...

Page 3: ...ilter pump off The unit should also switch off automatically 5 The unit and the filter pump should run 24 hours a day until the desired pool water temperature has been reached Once the set temperature is reached the unit will switch itself off As long as the filter pump is running the unit will restart automatically when the temperature of the pool water drops more than 1 C below the set temperatu...

Page 4: ...keep your desired pool temperature at all times Example If you want your pool to be 30 C A If the pool water is below 29 C the heat pump will start heating B When the temperature reaches 31 C the heat pump will stop C If the temperature in your pool continues to rise and passes 32 C the heat pump will start again BUT in Cooling Mode and cool down to 30 C D If now the temperature continues to drop ...

Page 5: ... MODE for 5 sec The display will start to blink both digits The first digit indicates the parameter The second digit s indicate the value of the parameter This reading mode will be deactivated if you do not press a button for 10 sec By pressing or you will see parameters from 0 to F one by one Make a note of each parameter for your records Wait 10 sec and this function is deactivated you are back ...

Page 6: ...flash to indicate that they can be modified by pressing or 2 Press again minute digits will flash to indicate that they can be modified by pressing or 3 Press again for final confirmation of time setting Once time has been set LED display will show time when heat pump is on standby ...

Page 7: ...to activate timer start or to activate timer stop the corresponding indicator light will be flashing Press to cancel timer start or timer stop INFO The parameter can be changed by a skilled person A code is needed to do so The procedure for this is in the Main Manual The keypad can be locked to prevent unauthorized use or changes of the heat pump The procedure for this is in the Main Manual If the...

Page 8: ...ilter unit water inlet on heat pump 3 Start the filter pump to start the water flow to the heat pump Adjust the by pass so there is enough water running through the heat pump Normally on a small filter system the by pass can be closed so all circulated water goes through the heat pump 4 Reconnect the electrical power supply to the heat pump and turn the heat pump ON 13 Check up Our heat pumps have...

Page 9: ...nning If the water stops running out it is condensation AN EVEN QUICKER WAY IS TO TEST THE DRAIN WATER FOR CHLORINE If no chlorine is detected the drain water is a result of condensation Also make sure that the air in and out passages are free and prevent air out from immediately re entering to the air in It is important to have min 2 5m free space at the air out side of the heat pump 14 Maintenan...

Page 10: ...10 The manometer is showing the pressure at 14 ambient air and the pump is not running standby mode ...

Page 11: ... heat pump to prevent damage to the compressor If the heat pump has been transported and carried all the time with the feet down it can be started immediately Note Switch off the power before carrying out any maintenance or repairs IMPORTANT REMARK if a malfunction cannot be resolved immediately in order to analyse the problem we will need to know the message error code that is showing on the disp...

Page 12: ...eeze protection for cooling Refer to PP06 Refer to PP06 PP07 PP7 Winter anti freeze protection Ⅰ No action required PP07 PP7 Winter anti freeze protection Ⅱ No action required EE03 EE3 Water flow switch failure 1 Check if wiring connection of flow switch is in correct position 2 Check water flow 3 Check if flow switch is broken 4 Check if water pump is working 1 Reconnect the wiring 2 Increase wat...

Page 13: ...13 ...

Page 14: ...Default Settings Observed Settings ____________________________________________ Is the heat pump Running __ Running sometimes __ Not running at all ___ Is the heat pump Heating __ Not Heating enough __ Not heating at all __ Is the fan running YES__ NO__ Is there ice on Radiator YES__ NO__ Is there Cold Air coming out from Radiator YES__ NO__ DON T KNOW__ Are there leaves or dirt on the fins on the...

Page 15: ... The heat pump stops Error code EE3 Too little water flow Check Filter and filter Pump Air in the Filter system Water Flow Switch defect d The heat pumps stops and starts frequently Too little water flow Air leakage in pipes on suction side Check Filter and filter Pump Air in the Filter system Water Flow Switch defect e Heat pump does not work periodically Weak power Supply To long Supply Cable To...

Page 16: ...16 ...

Reviews: