Chapter 7 - System Description
_______________________________________________________________________________________________________________
MNL000301.doc
Revision 2
01/04/2019
SourceSystem TE11
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
7
-
16
right corner of the Main screen. A time stamp of when the alarm occurred will be displayed with
each alarm.
The CONTROLLER STATUS box is located in the top center of the screen and displays the current
status of the process panel. Refer to Figure 7.7.
Figure 7.7:
Alarm and Controller Status Boxes
TFT LCD Display
The 10” TFT LCD display provides, through a lighted display, visual indication of
pneumatic valve positions. On a color screen, open valves are shown in red (default) and
closed valves are shown in green (default). The valve condition colors conform to ISA
standards. TE11 also provides the optional valve condition color to meet customers’
requirement.
Emergency Stop
The red, mushroom head push
‐
pull emergency stop button, located on the right side of the
cabinet controller, shuts off power to the pilot solenoids, closing all of the pneumatic
valves. Power is maintained to the controller, but it cannot open the valves until the button
is pulled out to its normal position. Refer to Chapter 8 Section1, Figure 8.1 for details on
the Emergency Stop pushbutton.
7.8
Main Menu Options
Note: The following descriptions of system sequences are not intended as a guide to
operation. Use specific operating procedures, provided in Chapter 8, to operate the
system.
The main menu provides access to Source Mode Menu and the Configuration Menu. It is
password
‐
protected. Contact your Versum Materials, Inc. Representative for your system
passwords.
7.8.1 Source Mode Menu Options