411
Symbol Math Instructions
Section 3-11
Description
*U(420) multiplies the binary values in Md and Mr and outputs the result to R,
R+1.
Flags
Precautions
When *U(422) is executed, the Error Flag will turn OFF.
If as a result of the multiplication, the content of R, R+1 is 0000 hex, the
Equals Flag will turn ON.
If as a result of the multiplication, the content of the leftmost bit of R+1 is 1,
the Negative Flag will turn ON.
Examples
When CIO 000000 is ON in the following example, D00100 and D00110 will
be multiplied as 4-digit unsigned binary values and the result will be output to
D00121 and D00120.
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_ 32767
(n = 0 to C)
Constants
#0000 to #FFFF
(binary)
---
Data Registers
DR0 to DR15
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area
Md
Mr
R
Md
Mr
R +1 R
×
(Unsigned binary)
(Unsigned binary)
(Unsigned binary)
Name
Label
Operation
Error Flag
ER
OFF
Equals Flag
=
ON when the result is 0.
OFF in all other cases.
Negative Flag
N
ON when the leftmost bit of the result is 1.
OFF in all other cases.