782
High-speed Counter/Pulse Output Instructions
Section 3-21
Ladder Symbol
Variations
Applicable Program Areas
Operands
P: Port Specifier
The port specifier specifies the port where the pulses will be output.
M :Output Mode
The value of M determines the output mode.
F: First Pulse Frequency Word
The value of F and F+1 sets the pulse frequency in Hz.
Operand Specifications
SPED(885)
P
M
F
P: Port specifier
M: Output mode
F: First pulse frequency word
Variations
Executed Each Cycle for ON Condition
SPED(885)
Executed Once for Upward Differentiation
@SPED(885)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
P
Port
0000 hex
Pulse output 0
0001 hex
Pulse output 1
Mode
0 hex: Continuous
1 hex: Independent
Direction
0 hex: CW
1 hex: CCW
Pulse output method (See note.)
0 hex: CW/CCW
1 hex: Pulse + direction
Always 0 hex.
Note: Use the same pulse output method when using both pulse outputs 0 a
0
3
4
7
8
11
12
15
M
F
F+1
Lower word of target frequency
Upper word of target frequency
0 to 100,000 Hz
(0000 0000 to 0001 86A0 hex)
0
15
Area
P
M
F
CIO Area
---
---
CIO 0000 to CIO 6142
Work Area
---
---
W000 to W510
Holding Bit Area
---
---
H000 to H510
Auxiliary Bit Area
---
---
A448 to A958
Timer Area
---
---
T0000 to T4094
Counter Area
---
---
C0000 to C4094