![Omron CJ1G-CPUxx Instructions Manual Download Page 960](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491960.webp)
939
Failure Diagnosis Instructions
Section 3-30
and the Error Log is becoming full of user-defined FAL(006) errors. The follow-
ing table shows the PLC Setup setting:
Even if PLC Setup word 129 bit 15 is set to 1 (Do not record FAL Errors in
Error Log.), the following errors will be recorded:
• Fatal errors generated by FALS(007)
• Non-fatal errors from the system
• Fatal errors from the system
• Non-fatal errors from the system generated intentionally with FAL(006) or
FPD(269)
• Fatal errors from the system generated intentionally with FALS(007)
Clearing Non-fatal Errors without a Programming Device
1.
Clearing User-defined Non-fatal Errors
When FAL(006) is executed with N set to 0, non-fatal errors can be cleared.
The value of S will determine the processing, as shown in the following ta-
ble.
2.
Clearing Non-fatal System Errors (CS1-H, CJ1-H, CJ1M, and CS1D CPU
Units Only)
There are two ways to clear non-fatal system errors generated with
FAL(006).
• Turn the PLC OFF and then ON again.
• When keeping the PLC ON, the system error must be cleared as if the
specified error had actually occurred.
Flags
Item
Setting
Programming Console
setting address
Word
129
Bit
15
Name
FAL Error Log Registration
Settings
0: Record FAL Errors in Error Log.
1: Do not record FAL Errors in Error Log.
Default setting
0: Record FAL Errors in Error Log.
Times that PLC Setup set-
ting is read
Every cycle (when an FAL Error occurs)
S
Process
&1 to &511 (0001 to 01FF hex) The FAL error of the specified number will be
cleared.
FFFF hex
All non-fatal errors (including system errors) will
be cleared.
0200 to FFFE hex or word
specification
T
he most serious non-fatal error (even if it is a
non-fatal system error) that has occurred.
When more than one FAL error has occurred,
the FAL error with the smallest FAL number will
be cleared.
Name
Label
Operation
Error Flag
ER
ON if N isn’t within the specified range of 0 to 511 deci-
mal.
ON if a non-fatal system error is being generated (CS1-H/
CJ1-H/CJ1M/CS1D Only), but the specified error code or
error details code is incorrect.
OFF in all other cases.
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...