970
Other Instructions
Section 3-31
The FRMCV(284) instruction can be used to convert a CV-series program
with the following two kinds of programming for use in a CS/CJ-series PLC.
See the Examples later in this section for an example.
1.
When using indirect binary mode DM addressing (
*
DM)
(when indirectly specifying a data area address with a PLC memory ad-
dress in DM)
2.
When using CV-series PLC memory addresses directly as values
(when storing PLC memory addresses in Index Registers with direct ad-
dressing using an instruction such as MOV(021))
Operand Specifications
Flags
Area
S
D
CIO Area
CIO 0000 to CIO 6143
---
Work Area
W000 to W511
---
Holding Bit Area
H000 to H511
---
Auxiliary Bit Area
A448 to A959
---
Timer Area
T0000 to T4095
---
Counter Area
C0000 to C4095
---
DM Area
D00000 to D32767
---
EM Area without bank
E00000 to E32767
---
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
---
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
---
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
---
Constants
Any constant except 09FF Hex, 0A00
to 0AFF Hex, or 0D00 to 0E3F Hex
---
Data Registers
DR0 to DR15
---
Index Registers
---
IR0 to IR15
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to
+2047 ,IR15
DR0 to DR15, IR0 to IR15
---
Name
Label
Operation
Error Flag
ER
ON if S specifies one of the following PLC memory
addresses that do not exist in the CS/CJ-series:
Temporary Relay (TR) Area (09FF Hex)
CPU Bus Link (G) Area (0A00 to 0AFF Hex)
SFC Areas (0D00 to 0E3F Hex)
OFF in all other cases.