![Omron CJ1G-CPUxx Instructions Manual Download Page 811](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491811.webp)
790
High-speed Counter/Pulse Output Instructions
Section 3-21
S: First Word of Settings Table
The contents of S to S+5 control the pulse output as shown in the following
diagrams.
The actual number of movement pulses that will be output are as follows:
For relative pulse output, the number of movement pulses = the set number of
pulses. For absolute pulse output, the number of movement pulses = the set
number of pulses
−
the PV.
F: First Word of Starting Frequency
The starting frequency is given in F and F+1.
Operand Specifications
S1+4
S1+5
Lower word with number of output pulses
Upper word with number of output pulses
Relative pulse output: 0 to 2,147,483,647
(0000 0000 to 7FFF FFFF hex)
Absolute pulse output: -2,147,483,648 to 2,147,483,647
(8000 0000 to 7FFF FFFF hex)
S1+2
S1+3
Lower word with target frequency
Upper word with target frequency
1 to 100,000 Hz
(0000 0000 to 0001 86A0 hex)
Specify the frequency after acceleration in Hz.
S1
S1+1
Acceleration rate
Deceleration rate
1 to 2,000 Hz (0001 to 07D0 hex)
1 to 2,000 Hz (0001 to 07D0 hex)
Specify the increase or decrease in the frequency per pulse control period (4 ms).
0
15
F
F+1
Lower word with starting frequency
Upper word with starting frequency
0 to 100,000 Hz
(0000 0000 to 0001 86A0 hex)
Specify the starting frequency in Hz.
0
15
Area
P
M
S
F
CIO Area
---
---
CIO 0000 to CIO 6138
CIO 0000 to CIO 6142
Work Area
---
---
W000 to W506
W000 to W510
Holding Bit Area
---
---
H000 to H506
H000 to H510
Auxiliary Bit Area
---
---
A448 to A954
A448 to A958
Timer Area
---
---
T0000 to T4090
T0000 to T4094
Counter Area
---
---
C0000 to C4090
C0000 to C4094
DM Area
---
---
D00000 to D32762
D00000 to D32766
EM Area without bank
---
---
---
---
EM Area with bank
---
---
---
---
Indirect DM/EM
addresses in binary
---
---
@ D00000 to @ D32767
@ D00000 to @ D32767
Indirect DM/EM
addresses in BCD
---
---
*D00000 to *D32767
*D00000 to *D32767
Constants
See description
of operand.
See description
of operand.
---
See description of oper-
and.
Data Registers
---
---
---
---
Summary of Contents for CJ1G-CPUxx