Table Data Processing Instructions
Section 3-17
3-17-11 FIND MINIMUM: MIN(183)
Purpose
Finds the minimum value in the range.
In CS1-H, CJ1-H, and CJ1M CPU Units, this instruction can be run in the
background. Refer to the CS/CJ Series Programmable Controllers Program-
ming Manual for details on background execution.
Ladder Symbol
Variations
Applicable Program Areas
Operands
C and C+1: Control words
C specifies the number of words in the range, bit 15 of C+1 indicates whether
the data will be treated as signed binary or unsigned binary, and bit 14 of C+1
indicates whether or not to output the PLC memory address of the word that
contains the minimum value to IR00.
Note C and C+1 must be in the same data area.
The following table shows the possible values of C.
C: First control word
R1: First word in range
D: Destination word
MIN(183)
C
R1
D
Variations
Executed Each Cycle for ON Condition
MIN(183)
Executed Once for Upward Differentiation
@MIN(183)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
C+1
Data type
Index Register output
0000
Unsigned binary
No
4000
Unsigned binary
Yes
Number of words in range
Output selection
0: Does not output address to IR00.
1: Outputs address to IR00.
Data type
0: Unsigned binary data
1: Signed binary data
15
0
C
15
0
14
0
C+1
13
00
0000
0000
0000