955
Failure Diagnosis Instructions
Section 3-30
Register words R+2 through R+5 would have the following values for W51115:
The user can store an ASCII message in register words R+6 to R+10. This
message will be displayed on the Programming Device if a non-fatal error is
generated by the time monitoring function. Mark the end of the message with
the null character (00 hexadecimal).
Disabling Error Log
Entries of Non-fatal
FPD(269) Errors
(CS1-H, CJ1-H, CJ1M, or
CS1D Only)
Normally when the FPD(269) Time Monitoring Function generates a non-fatal
error, the error code and the time that the error occurred are written to the
Error Log Area (A100 through A199). In CS1-H, CJ1-H, CJ1M, and CS1D
CPU Units, it is possible to set the PLC Setup so that the non-fatal errors gen-
erated by FAL(006) are not recorded in the Error Log.
Even though the error will not be recorded in the Error Log, the FAL Error Flag
(40215) will be turned ON, the corresponding flag in the Executed FAL Num-
ber Flags (A36001 to A39115) will be turned ON, and the error code will be
written to A400.
Disable Error Log entries for FPD(269) time-monitoring errors when you want
to record only the system-generated errors. For example, this function is use-
ful during debugging if the FPD(269) and FAL(006) instructions are used in
several applications and the Error Log is becoming full of these errors. The fol-
lowing table shows the PLC Setup setting:
Even if PLC Setup word 129 bit 15 is set to 1 (Do not record FAL Errors in
Error Log.), the following errors will be recorded:
• Fatal errors generated by FALS(007)
• Non-fatal errors from the system
• Fatal errors from the system
• Non-fatal errors from the system generated intentionally with FAL(006) or
FPD(269)
• Fatal errors from the system generated intentionally with FALS(007)
Word
Bits 8 to 15
Bits 0 to 7
R+2
W
5
R+3
1
1
R+4
1
5
R+5
2D (hexadecimal)
Input type (hexadecimal)
30: Normally open
31: Normally closed
15
8
0
7
R+6
R+7
R+8
R+9
R+10
Item
Setting
Programming Console
setting address
Word
129
Bit
15
Name
FAL Error Log Registration
Settings
0: Record FAL Errors in Error Log.
1: Do not record FAL Errors in Error Log.
Default setting
0: Record FAL Errors in Error Log.
Times that PLC Setup set-
ting is read
Every cycle (when an FAL Error occurs)