837
Basic I/O Unit Instructions
Section 3-23
When the input condition is met, self maintenance is performed by output A
and IOWR(223) is executed with each cycle until the Equals Flag turns ON.
When the writing is completed and the Equals Flag turns ON, output B turns
ON and the self maintenance is cleared.
Be sure to place condition flags directly after IOWR(223) instructions, and not
after any other instructions. If a condition flag is placed after another instruc-
tion, it will be affected by the execution results of that instruction.
Example
In this example, IOWR(223) is used to write data.
3-23-5 CPU BUS UNIT I/O REFRESH: DLNK(226)
Purpose
Performs I/O refreshing immediately for the CPU Bus Unit with the specified
unit number. The following data is refreshed:
• The words allocated to the CPU Bus Unit in the PLC’s CPU Bus Unit
Areas (25 words in the CIO Area and 100 words in the DM Area)
• Specific data refreshing for Units such as Units that support data links
This instruction is supported by the CS1-H, CJ1-H, CJ1M, and CS1D CPU
Units only.
B
IOWR
C
S
=
B
D
A
A
D+1
D
Unit number: 3
Number of words
to transfer: 10
When CIO 000000 is turned ON, the 10 words in D00100
to D00109 are written to the Special I/O Unit.
CPU Unit
Special I/O Unit (Unit #3)
The control code (C) varies depending on the Special I/O Unit.
10 words
D