![Omron CJ1G-CPUxx Instructions Manual Download Page 1025](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_7424911025.webp)
1004
Block Programming Instructions
Section 3-32
Program execution will flow from 2 to 3 to 4 and back to 2 during the 7,000
counts before “B” is executed, as shown in the following diagram.
3-32-9 HIGH-SPEED TIMER WAIT: TMHW(815) and TMHWX(817)
Purpose
Delays execution of the rest of the block program until the specified time has
elapsed. Execution will be continued from the next instruction after
TMHW(815)/TMHWX(817) when the timer times out.
Ladder Symbol
PV Refresh Method: BCD
PV Refresh Method: Binary
Variations
Address
Instruction
Operand
000200
LD
000000
000201
BPRG
0
.
.
A
.
.
000210
CNTW
0005
#7000
000100
.
.
B
.
.
000220
BEND
---
Counter counts out.
CIO 000100
counted.
Updated
Updated
0
1
4
2
3
N: Timer number
SV: Set value
TMHW(815) N
SV
N
: Timer number
SV
: Set value
TMHWX(817) N
SV
Variations
Always Executed in Block Program
Summary of Contents for CJ1G-CPUxx