770
High-speed Counter/Pulse Output Instructions
Section 3-21
C: Control Data
The function of INI(880) is determined by the control data, C.
NV: First Word with New PV
NV and NV+1 contain the new PV when changing the PV.
If C is 0002 hex (i.e., when changing a PV), NV and NV+1 contain the new PV.
Any values in NV and NV+1 are ignored when C is not 0002 hex.
Operand Specifications
0100 hex
Interrupt input 0 in counter mode
0101 hex
Interrupt input 1 in counter mode
0102 hex
Interrupt input 2 in counter mode
0103 hex
Interrupt input 3 in counter mode
1000 hex
PWM(891) output 0
1001 hex
PWM(891) output 1
C
INI(880) function
0000 hex
Starts comparison.
0001 hex
Stops comparison.
0002 hex
Changes the PV.
0003 hex
Stops pulse output.
P
Port
S
S+1
Lower word of new PV
Upper word of new PV
0
15
For Pulse Output or High-speed Counter Input:
0000 0000 to FFFF FFFF hex
For Interrupt Input in Counter Mode:
0000 0000 to 0000 FFFF hex
Area
P
C
NV
CIO Area
---
---
CIO 0000 to CIO 6142
Work Area
---
---
W000 to W510
Holding Bit Area
---
---
H000 to H510
Auxiliary Bit Area
---
---
A448 to A958
Timer Area
---
---
T0000 to T4094
Counter Area
---
---
C0000 to C4094
DM Area
---
---
D00000 to D32766
EM Area without bank
---
---
---
EM Area with bank
---
---
---
Indirect DM/EM
addresses in binary
---
---
@ D00000 to @ D32767
Indirect DM/EM
addresses in BCD
---
---
*D00000 to *D32767
Constants
See descrip-
tion of oper-
and.
See descrip-
tion of oper-
and.
---
Data Registers
---
---
---