![Omron CJ1G-CPUxx Instructions Manual Download Page 796](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491796.webp)
775
High-speed Counter/Pulse Output Instructions
Section 3-21
Description
PRV(881) reads the data specified in C for the port specified in P. The possi-
ble combinations of data and ports are shown in the following table.
■
Reading a PV (C = 0000 hex)
If C is 0000 hex, PRV(881) reads a PV as shown in the following table.
Indirect DM/EM
addresses in binary
---
---
@ D00000 to @ D32767
Indirect DM/EM
addresses in BCD
---
---
*D00000 to *D32767
Constants
See descrip-
tion of oper-
and.
See descrip-
tion of oper-
and.
---
Data Registers
---
---
---
Index Registers
---
---
---
Indirect addressing
using Index Registers
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –
2048 to +2047 ,IR15
DR0 to DR15, IR0 to
IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area
P
C
D
P: Port specifier
C: Control data
0000 hex:
Read PV
0001 hex:
Read status
0002 hex:
Read range
comparison
results
0003 hex:
Read high-
speed
counter
frequency
0000 or 0001 hex:
Pulse output
OK
OK
Not allowed.
Not allowed.
0010 or 0011 hex:
High-speed counter
input
OK
OK
OK
OK (high-
speed
counter 0
only)
0100, 0101, 0102, or
0103 hex: Interrupt
input in counter mode
OK
Not allowed.
Not allowed.
Not allowed.
1000 or 1001 hex:
PWM (891) output
Not allowed.
OK
Not allowed.
Not allowed.
Port and mode
Operation
Setting range
Pulse output (P =
0000 or 0001 hex)
The present value of the
pulse output is stored in
D and D+1.
8000 0000 to 7FFF FFFF hex
(-2,147,483,648 to
2,147,483,647)
High-speed
counter
input (P =
0010 or
0011 hex)
Linear
Mode
The present value of the
high-speed counter is
stored in D and D+1.
8000 0000 to 7FFF FFFF hex
(-2,147,483,648 to
2,147,483,647)
Ring
Mode
0000 0000 to FFFF FFFF hex
(0 to 4,294,967,295)
Interrupt inputs in
counter mode
(P = 0100, 0101,
0102, or 0103 hex)
The present value of the
interrupt input is stored
in D.
0000 to FFFF hex