Block Programming Instructions
Section 3-32
Description
Operation without an Operand
If an operand bit is not specified, an execution must be created before
WAIT(805)/WAIT(805 NOT starting with LD. If the execution condition is ON
for WAIT(805), the rest of the instruction in the block program will be skipped.
In the next cycle, none of the block program will be executed except for the
execution condition for WAIT(805). When the execution condition goes ON,
the instruction from WAIT(805) to the end of the program will be executed.
Operation with an Operand
An operand bit, B, can be specified for WAIT(805) or WAIT NOT(805). If the
operand bit is OFF (ON for WAIT NOT(805)), the rest of the instructions in the
block program will be skipped. In the next cycle, none of the block program will
be executed except for the execution condition for WAIT(805) or WAIT(805)
NOT. When the execution condition goes ON (OFF for WAIT(805) NOT), the
instruction from WAIT(805) or WAIT(805) NOT to the end of the program will
be executed.
EM Area without bank
---
EM Area with bank
---
Indirect DM/EM
addresses in binary
---
Indirect DM/EM
addresses in BCD
---
Constants
---
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area
B
Execution
condition
Execution
condition
OFF
Execution
condition
OFF
Execution
condition
ON
"A"
executed.
"B" executed.
"C"
executed.
"C"
executed.
"C" executed.
Wait