![Omron CJ1G-CPUxx Instructions Manual Download Page 213](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491213.webp)
192
Sequence Control Instructions
Section 3-5
Operands
N: Jump Number
The jump number must be 0000 to 03FF (0 to 1,023 decimal).
Operand Specifications
Description
When the execution condition for JMP(004) is ON, no jump is made and the
program is executed consecutively as written.
When the execution condition for JMP(004) is OFF, program execution jumps
directly to the first JME(005) in the program with the same jump number. The
instructions between JMP(004) and JME(005) are not executed, so the status
of outputs between JMP(004) and JME(005) is maintained. In block programs,
the instructions between JMP(004) and JME(005) are skipped regardless of
the status of the execution condition.
Area
N
JMP(004)
JME(005)
CIO Area
CIO 0000 to CIO 6143
---
Work Area
W000 to W511
---
Holding Bit Area
H000 to H511
---
Auxiliary Bit Area
A000 to A959
---
Timer Area
T0000 to T4095
---
Counter Area
C0000 to C4095
---
DM Area
D00000 to D32767
---
EM Area without bank
E00000 to E32767
---
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
---
Indirect DM/EM addresses
in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to
@ En_32767
(n = 0 to C)
---
Indirect DM/EM addresses
in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
---
Constants
#0000 to #03FF (binary) or
&0 to &1023
#0000 to #03FF (binary) or
&0 to &1023
Data Registers
DR0 to DR15
---
Index Registers
---
---
Indirect addressing using
Index Registers
,IR0 to ,IR15
–2048 to +2047, IR0 to
–2048 to +2047, IR15
DR0 to DR15, IR0 to IR15
---
Execution condition
Instructions
executed
Instructions
jumped
Instructions in this section are not
executed and output status is main
tained. The instruction execution time
for these instructions is eliminated.
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...