Instruction Functions
Section 2-2
ACCUMULATIVE
TIMER
TTIM
087
(BCD)
TTIMX
555
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
LONG TIMER
TIML
542
(BCD)
TIMLX
553
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
Instruction
Mnemonic
Code
Symbol/Operand
Function
Location
Execution
condition
Page
N: Timer number
S: Set value
TTIM(087)
N
S
Timer
input
Reset
input
Timer input
Timer PV
SV
Completion
Flag
Reset input
PV maintained.
Timing resumes.
TTIM(087)/TTIMX(555) operates an incrementing timer with units of
0.1-s. The setting range for the set value (SV) is 0 to 999.9 s for
BCD and 0 to 6,553.5 s for binary (decimal or hexadecimal).
N: Timer number
S: Set value
TTIMX(555)
N
S
Timer
input
Reset
input
D1: Completion
Flag
D2: PV word
S: SV word
TIML(542)
D1
D2
S
Timer input
Timer PV
SV
Completion Flag
(Bit 00 of D1)
TIML(542)/TIMLX(553) operates a decrementing timer with units of
0.1-s that can time up to approx. 115 days for BCD and 49,710 days
for binary (decimal or hexadecimal).
D1: Completion
Flag
D2: PV word
S: SV word
TIMLX(553)
D1
D2
S