441
Conversion Instructions
Section 3-12
Applicable Program Areas
Operands
S: Source Word
The data in the source word indicates the location of the bit(s) that will be
turned ON.
C: Control Word
The control word specifies whether MLPX(076) will perform a 4-to-16 bit con-
version or an 8-to-256 bit conversion, the number of digits or bytes to be con-
verted, and the starting digit or byte.
R: First result word
There can be anywhere from 1 to 32 result words, depending upon the type of
conversion process and number of digits/bytes being converted. The result
words must be in the same data area.
Operand Specifications
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Specifies the first digit/byte to be converted
4-to-16: 0 to 3 (digit 0 to 3)
8-to-256: 0 or 1 (byte 0 or 1)
Number of digits/bytes to be converted
4-to-16: 0 to 3 (1 to 4 digits)
8-to-256: 0 or 1 (1 or 2 bytes)
Conversion process
0: 4-to-16 bits (digit to word)
1: 8-to-256 bits (byte to 16-word range)
Digit number: 3 2 1 0
0
Area
S
C
R
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
---
Specified values
only
---
Data Registers
DR0 to DR15
---