![Omron CJ1G-CPUxx Instructions Manual Download Page 175](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491175.webp)
154
Sequence Input Instructions
Section 3-3
In the following diagram, the two logic blocks are indicated by dotted lines.
Studying this example shows that an ON execution condition will be produced
when either of the execution conditions in the left logic block is ON (i.e., when
either CIO 000000 or CIO 000001 is ON) and either of the execution condi-
tions in the right logic block is ON (i.e., when either CIO 000002 is ON or
CIO 000003 is OFF).
Flags
There are no flags affected by this instruction.
Precautions
Three or more logic blocks can be connected in series using this instruction to
first connect two of the logic blocks and then to connect the next and subse-
quent ones in order. It is also possible to continue placing this instruction after
three or more logic blocks and connect them together in series.
When a logic block is connected by AND LOAD or OR LOAD instructions, the
total number of AND LOAD/OR LOAD instructions must match the total num-
ber of LOAD/LOAD NOT instructions minus 1. If they do not match, a program
error will occur.
Example
Coding Example (1)
Coding Example (2)
Instruction
Operand
LD
000000
OR NOT
000001
LD NOT
000002
OR
000003
AND LD
---
LD
000004
OR
000005
AND LD
---
.
.
.
.
OUT
000500
Instruction
Operand
LD
000000
OR NOT
000001
LD NOT
000002
OR
000003
LD
000004
OR
000005
.
.
.
.
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...