![Omron CJ1G-CPUxx Instructions Manual Download Page 207](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491207.webp)
186
Sequence Control Instructions
Section 3-5
3-5
Sequence Control Instructions
3-5-1
END: END(001)
Purpose
Indicates the end of a program.
Ladder Symbol
Variations
Applicable Program Areas
Description
END(001) completes the execution of a program for that cycle. No instructions
written after END(001) will be executed.
Execution proceeds to the program with the next task number. When the pro-
gram being executed has the highest task number in the program, END(001)
marks the end of the overall main program.
Precautions
Always place END(001) at the end of each program. A programming error will
occur if there isn’t an END(001) instruction in the program.
END(001)
Variations
Executed Each Cycle for ON Condition
END(001)
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
Not allowed
Not allowed
OK
Task 1
Program A
To the next task number
Task 2
Program B
To the next task number
Task n
Program Z
I/O refreshing
End of the main program