32
Instruction Functions
Section 2-2
2-2-4
Timer and Counter Instructions
Instruction
Mnemonic
Code
Symbol/Operand
Function
Location
Execution
condition
Page
TIMER
TIM
(BCD)
TIMX
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
HIGH-SPEED
TIMER
TIMH
015
(BCD)
TIMHX
551
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
ONE-MS TIMER
TMHH
540
(BCD)
TMHHX
552
(BCD)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
TMHH(540)/TMHHX(552) operates a decrementing timer with units of
1-ms. The setting range for the set value (SV) is 0 to 9.999 s for BCD
and 0 to 65.535 s for binary (decimal or hexadecimal).
The timing charts for TMHH(540) and TMHHX(552) are the same as
those given above for TIMH(015).
Output
Required
N: Timer number
S: Set value
TIM
N
S
Timer input
Timer PV
SV
Completion
Flag
Timer input
Timer PV
SV
Completion
Flag
TIM/TIMX(550) operates a decrementing timer with units of 0.1-s.
The setting range for the set value (SV) is 0 to 999.9 s for BCD
and 0 to 6,553.5 s for binary (decimal or hexadecimal).
N: Timer number
S: Set value
TIMX(550)
N
S
N: Timer number
S: Set value
TIMH(015)
N
S
Timer input
Timer PV
SV
Completion
Flag
Timer input
Timer PV
SV
Completion
Flag
TIMH(015)/TIMHX(551) operates a decrementing timer with units
of 10-ms. The setting range for the set value (SV) is 0 to 99.99 s
for BCD and 0 to 655.35 s for binary (decimal or hexadecimal).
N: Timer number
S: Set value
TIMHX(551)
N
S
N: Timer number
S: Set value
TMHH(540)
N
S
N: Timer number
S: Set value
TMHHX(552)
N
S