![Omron CJ1G-CPUxx Instructions Manual Download Page 332](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491332.webp)
311
Data Shift Instructions
Section 3-9
Variations
Applicable Program Areas
Operands
C: Control Word
Note St and E must be in the same data area.
Operand Specifications
Variations
Executed Each Cycle for ON Condition
SFTR(084)
Executed Once for Upward Differentiation
@SFTR(084)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
15 14 13 12
Shift direction
1 (ON): Left
0 (OFF): Right
Data input
Reset
Shift input
Area
C
St
E
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
---
Data Registers
DR0 to DR15
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047, IR0 to –2048 to +2047, IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...