![Omron CJ1G-CPUxx Instructions Manual Download Page 771](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491771.webp)
750
Interrupt Control Instructions
Section 3-20
in the PLC Setup. If cyclic refreshing with the Special I/O Unit isn’t disabled,
IORF(097) might be executed during cyclic refreshing resulting in a non-fatal
Duplicate Refresh Error and turning ON the Interrupt Task Error Flag
(A40213).
Examples
Examples for CS1W-INT01/CJ1W-INT01
When CIO 000000 turns ON in the following example, MSKS(690) unmasks
(enables) interrupt inputs in Interrupt Input Unit 0.
When CIO 000001 turns ON in the following example, MSKS(690) sets the
rising/falling edge designations for Interrupt Input Unit 0.
Example for C200HS-INT01
When CIO 000000 turns ON in the following example, MSKS(690) unmasks
(enables) interrupt inputs 1, 3, and 5 in Interrupt Input Unit 2.
Example for Scheduled Interrupts
When CIO 000001 is ON in the following example, MSKS(690) sets a 10-sec-
ond time interval for scheduled interrupt 2. (In this case, the scheduled time
interval units are set to 10 ms in the PLC Setup.)
3-20-2 READ INTERRUPT MASK: MSKR(692)
Purpose
Reads the current interrupt processing settings that were set with
MSKS(690).
MSKR(692) is not supported by the CS1D CPU Units.
Ladder Symbol
MSKS
0
D00100
000000
N
S
0
0
1
1
15
14
13
12
1
1
1
1
11
10
9
8
0
0
1
0
7
6
5
4
0
1
1
1
3
2
1
0
3
F
2
7
D00100
0: Enabled
1: Masked
MSKS
2
D00101
000001
N
S
0
0
0
0
15
14
13
12
0
1
0
1
11
10
9
8
0
0
0
0
7
6
5
4
0
0
1
0
3
2
1
0
0
5
0
2
D00101
0: Rising edge
1: Falling edge
N: Interrupt identifier
D: Destination word
MSKR(692)