713
Data Control Instructions
Section 3-18
Operands
The contents of the five words starting with the first parameter word (P1) are
shown in the following diagram.
Note P1 to P1+4 must be in the same area.
Operand Specifications
Offset of linear function
8000 to 7FFF (signed binary)
∆
Y
8000 to 7FFF (signed binary)
∆
X
0001 to 9999 (BCD)
P1
P1+1
P1+2
P1+3
P1+4
Maximum conversion
8000 to 7FFF (signed binary)
Minimum conversion
8000 to 7FFF (signed binary)
15
0
15
0
15
0
15
0
15
0
Area
S
P1
R
CIO Area
CIO 0000 to CIO
6143
CIO 0000 to CIO
6139
CIO 0000 to CIO
6143
Work Area
W000 to W511
W000 to W507
W000 to W511
Holding Bit Area
H000 to H511
H000 to H507
H000 to H511
Auxiliary Bit Area
A000 to A447
A448 to A959
A000 to A443
A448 to A955
A448 to A959
Timer Area
T0000 to T4095
T0000 to T4091
T0000 to T4095
Counter Area
C0000 to C4095
C0000 to C4091
C0000 to C4095
DM Area
D00000 to
D32767
D00000 to
D32763
D00000 to
D32767
EM Area without bank
E00000 to
E32767
E00000 to
E32763
E00000 to
E32767
EM Area with bank
En_00000 to
En_32767
(n = 0 to C)
En_00000 to
En_32763
(n = 0 to C)
En_00000 to
En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)