![Omron CJ1G-CPUxx Instructions Manual Download Page 220](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491220.webp)
199
Sequence Control Instructions
Section 3-5
Note For CJPN(511), the ON/OFF status of CIO 000000 would be reversed.
3-5-6
MULTIPLE JUMP and JUMP END: JMP0(515) and JME0(516)
Purpose
When the execution condition for JMP0(515) is OFF, all instructions from
JMP0(515) to the next JME0(516) in the program are processed as
NOP(000). Use JMP0(515) and JME0(516) in pairs. There is no limit on the
number of pairs that can be used in the program.
Ladder Symbols
Variations
Applicable Program Areas
CIO 000000
OFF
CIO 000000
ON
Normal
execution
Instructions
not
executed.
(Outputs re-
main un-
changed.)
&1
&1
JMP0(515)
JME0(516)
Variations
Jumps when OFF/Doesn’t jump when ON
JMP0(515)
Immediate Refreshing Specification
Not supported
Variations
Executed Each Cycle for ON Condition
JME0(516)
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
Not allowed
OK