![Omron CJ1G-CPUxx Instructions Manual Download Page 950](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491950.webp)
929
Clock Instructions
Section 3-28
The following table shows the structure of the Calendar/Clock Area.
Operand Specifications
Description
DATE(735) changes the internal clock setting according to the clock data in
the four source words. The new internal clock setting is immediately reflected
in the Calendar/Clock Area (A351 to A354).
Addresses
Contents
A35100 to A35107
Second (00 to 59, BCD)
A35108 to A35115
Minute (00 to 59, BCD)
A35200 to A35207
Hour (00 to 23, BCD)
A35208 to A35215
Day of month (01 to 31, BCD)
A35300 to A35307
Month (01 to 12, BCD)
A35308 to A35315
Year (00 to 99, BCD)
A35400 to A35407
Day of week (00 to 06 = Sunday to Saturday, hexadecimal)
A35408 to A35415
Always set to 00.
Area
S
CIO Area
CIO 0000 to CIO 6140
Work Area
W000 to W508
Holding Bit Area
H000 to H508
Auxiliary Bit Area
A000 to A956
Timer Area
T0000 to T4092
Counter Area
C0000 to C4092
DM Area
D00000 to D32764
EM Area without bank
E00000 to E32764
EM Area with bank
En_00000 to En_32764
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
Constants
---
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
CPU Unit
Internal clock
New setting
Minutes Seconds
Day Hour
Year Month
00
Day of week
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...