434
Conversion Instructions
Section 3-12
Applicable Program Areas
Operands
S: First Source Word
The content of S+1 and S must be between 0000 0000 and 05F5 E0FF hexa-
decimal (0000 0000 and 9999 9999 decimal).
Operand Specifications
Description
BCDL(059) converts the 8-digit hexadecimal (32-bit binary) data in S and S+1
to 8-digit BCD data and writes the result to R and R+1.
Flags
Precautions
The content of S+1 and S must not exceed 05F5 E0FF (9999 9999 decimal).
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Area
S
R
CIO Area
CIO 0000 to CIO 6142
Work Area
W000 to W510
Holding Bit Area
H000 to H510
Auxiliary Bit Area
A000 to A958
A448 to A958
Timer Area
T0000 to T4094
Counter Area
C0000 to C4094
DM Area
D00000 to D32766
EM Area without bank
E00000 to E32766
EM Area with bank
En_00000 to En_32766
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
---
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
R
R+1
(BCD)
(BCD)
S+1
S
(BIN)
(BIN)
Name
Label
Operation
Error Flag
ER
ON if the contents of S and S+1 exceed 05F5 E0FF
(9999 9999 decimal).
OFF in all other cases.
Equals Flag
=
ON if the result is 0.
OFF in all other cases.