![Omron CJ1G-CPUxx Instructions Manual Download Page 754](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491754.webp)
733
Subroutines
Section 3-19
Operands
N: Global subroutine number
Specifies the global subroutine number between 0 and 1023 decimal.
Operand Specifications
Description
GSBS(750) calls the global subroutine with the specified global subroutine
number. The global subroutine is the program section between GSBN(751)
and GRET(752). When the global subroutine is completed, program execution
continues with the next instruction after GSBS(750).
This instruction can be written into multiple tasks with the same global subrou-
tine number to call that program from the different tasks. The program can be
modularized by making global subroutines into standard subroutines that are
common to many tasks.
The global subroutine region (between GSBN(751) and GRET(752)) must be
defined in interrupt task 0. If it is defined in another task, an error will occur
and the Error Flag will be turned ON when the GSBS(750) instruction is exe-
cuted.
The GSBS(750) instruction can be written in both cyclic tasks (including extra
cyclic tasks) and interrupt tasks.
Area
N
CIO Area
---
Work Area
---
Holding Bit Area
---
Auxiliary Bit Area
---
Timer Area
---
Counter Area
---
DM Area
---
EM Area without bank
---
EM Area with bank
---
Indirect DM/EM
addresses in binary
---
Indirect DM/EM
addresses in BCD
---
Constants
0 to 1023 (decimal)
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
---
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...