468
Conversion Instructions
Section 3-12
3-12-16 SIGNED BINARY-TO-BCD: BCDS(471)
Purpose
Converts one word of signed binary data to one word of signed BCD data.
Ladder Symbol
Variations
Applicable Program Areas
Operand
C: Control Word
Specifies the signed BCD format. C must be 0000 to 0003.
S: Source Word
Contains the signed binary data to be converted. The content of S must be
within the valid range of the BCD format specified in C.
D: Destination word
Contains the converted signed BCD data. See the description section below
for an explanation of the BCD formats.
Operand Specifications
C: Control word
S: Source word
D: Destination word
BCDS(471)
C
S
D
Variations
Executed Each Cycle for ON Condition
BCDS(471)
Executed Once for Upward Differentiation
@BCDS(471)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Setting
Allowed values for S
C=0000
FC19 to FFFF or 0000 to 03E7
C=0001
E0C1 to FFFF or 0000 to 1F3F
C=0002
FC19 to FFFF or 0000 to 270F
C=0003
F831 to FFFF or 0000 to 270F
Area
C
S
D
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)