![Omron CJ1G-CPUxx Instructions Manual Download Page 963](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491963.webp)
942
Failure Diagnosis Instructions
Section 3-30
3.
The CPU Bus Unit Setup Error Flag (A40203) and CPU Bus Unit Setup Er-
ror Flag for unit number 1 (A42701) will be turned ON.
4.
The CPU Unit’s ERR Indicator will flash.
5.
A message (CPU BU ST ERR 01) will be displayed at the Programming
Console indicating that an error has occurred with CPU Bus Unit 1.
3-30-2 SEVERE FAILURE ALARM: FALS(007)
Purpose
Generates user-defined fatal errors. Fatal errors stop PLC operation.
With CS1-H, CJ1-H, CJ1M, and CS1D CPU Units, FALS(007) can also be
used to generate fatal system errors.
Ladder Symbol
• Generating User-defined Fatal Errors
• Generating Fatal System Errors (CS1-H, CJ1-H, CJ1M, or CS1D Only)
Variations
Applicable Program Areas
MOV
#000A
A529
000A
A529CH
S : D00200
D00201
0400
0001
000000
FAL
10
D00200
N
S
Error code: 0400 (CPU Bus Unit Setup Error)
Matching
values
Error unit number: 1
FALS(007)
N
S
N: FALS number
S: First message word or
constant (0000 to FFFF)
FALS(007)
N
S
N: FALS number (value in A529)
S: First word containing the error
code and error details
Variations
Executed Each Cycle for ON Condition
FALS(007)
Executed Once for Upward Differentiation
Not supported.
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK