![Omron CJ1G-CPUxx Instructions Manual Download Page 314](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491314.webp)
293
Data Movement Instructions
Section 3-8
Variations
Applicable Program Areas
Operands
N: Number of Words
Specifies the number of words to be transferred. The possible range for N is
0000 to FFFF (0 to 65,535 decimal).
S: First Source Word
Specifies the first source word. S and S+(N–1) must be in the same data area.
D: First Destination Word
Specifies the first destination word. D and D+(N–1) must be in the same data
area.
Operand Specifications
Variations
Executed Each Cycle for ON Condition
XFER(070)
Executed Once for Upward Differentiation
@XFER(070)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
S+(N
−
1)
15
0
S
to
to
D+(N
−
1)
to
15
0
D
to
Area
N
S
D
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
#0000 to #FFFF
(binary) or &0 to
&65535
---
---
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...