![Omron CJ1G-CPUxx Instructions Manual Download Page 1126](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_7424911126.webp)
1105
CJ-series Instruction Execution Times and Number of Steps
Section 4-2
4-2-28 Failure Diagnosis Instructions
Note When a double-length operand is used, add 1 to the value shown in the length
column in the following table.
4-2-29 Other Instructions
Note When a double-length operand is used, add 1 to the value shown in the length
column in the following table.
Instruction
Mnemonic
Code
Length
(steps)
(See
note.)
ON execution time (
µ
s)
Conditions
CPU6
@
H CPU4
@
H
CPU4
@
CJ1M
FAILURE
ALARM
FAL
006
3
15.4
16.7
16.7
26.1
Recording errors
179.8
244.8
244.8
294.0
Deleting errors (in order
of priority)
432.4
657.1
657.1
853.3
Deleting errors (all errors)
161.5
219.4
219.4
265.7
Deleting errors (individu-
ally)
SEVERE
FAILURE
ALARM
FALS
007
3
---
---
---
---
---
FAILURE
POINT
DETECTION
FPD
269
4
140.9
202.3
202.3
220.7
When executed
163.4
217.6
217.6
250.3
First time
185.2
268.9
268.9
220.7
When executed
207.5
283.6
283.6
320.7
First time
Instruction
Mnemonic
Code
Length
(steps)
(See
note.)
ON execution time (
µ
s)
Conditions
CPU6
@
H CPU4
@
H
CPU4
@
CJ1M
SET CARRY
STC
040
1
0.06
0.06
0.12
0.15
---
CLEAR CARRY
CLC
041
1
0.06
0.06
0.12
0.15
---
SELECT EM BANK
EMBC
281
2
14.0
15.1
15.1
---
---
EXTEND MAXIMUM
CYCLE TIME
WDT
094
2
15.0
19.7
19.7
23.6
---
SAVE CONDITION
FLAGS
CCS
282
1
8.6
12.5
---
14.2
---
LOAD CONDITION
FLAGS
CCL
283
1
9.8
13.9
---
16.3
---
CONVERT ADDRESS
FROM CV
FRMCV
284
3
13.6
19.9
---
23.1
---
CONVERT ADDRESS TO
CV
TOCV
285
3
11.9
17.2
---
22.5
---
DISABLE PERIPHERAL
SERVICING
IOSP
287
---
13.9
19.8
---
21.5
---
ENABLE PERIPHERAL
SERVICING
IORS
288
---
63.6
92.3
---
22.2
---
Summary of Contents for CJ1G-CPUxx