708
Data Control Instructions
Section 3-18
Reverse Scaling
Reverse scaling can also be used by setting As < Bs and Ar > Br. The follow-
ing relationship will result.
Reverse scaling can be used, for example, to convert (reverse scale) 1 to 5 V
(0000 to 0FA0 hexadecimal) to 0300 to 0000, respectively, as shown in the fol-
lowing diagram.
3-18-7 SCALING 2: SCL2(486)
Purpose
Converts signed binary data into signed BCD data according to the specified
linear function. An offset can be input in defining the linear function.
Ladder Symbol
Variations
Applicable Program Areas
R (unsigned BCD)
Point A
Point B
S (unsigned binary)
R
Point A
Point B
S: Source word
P1: First parameter word
R: Result word
SCL2(486)
S
P1
R
Variations
Executed Each Cycle for ON Condition
SCL2(486)
Executed Once for Upward Differentiation
@SCL2(486)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program
areas
Step program
areas
Subroutines
Interrupt tasks
OK
OK
OK
OK