864
Serial Communications Instructions
Section 3-24
Operands
The contents of the control word, C, are as shown below.
Operand Specifications
Description
STUP(237) writes 10 words of data from S to S+9 to the communications
setup area of the Unit with the specified unit address, as shown in the follow-
Serial port number
1 hex: Peripheral port on CPU Unit or Port 1 on CPU Bus Unit or Inner Board
2 hex: Built-in RS-232C port on CPU Unit or Port 2 on CPU Bus Unit or Inner Board
(Settings 3 and 4 hex are reserved.)
Always set to 0.
Unit address of port device
CPU Unit: 00 hex
CPU Bus Unit: Unit 10 hex
Inner Board: E1 hex (CS Series only)
15
8
0
11
7
12
C
Area
C
S
CIO Area
CIO 0000 to CIO 6143
CIO 0000 to CIO 6134
Work Area
W000 to W511
W000 to W502
Holding Bit Area
H000 to H511
H000 to H502
Auxiliary Bit Area
A000 to A438
A448 to A959
A000 to A438
A448 to A950
Timer Area
T0000 to T4095
T0000 to T4086
Counter Area
C0000 to C4095
C0000 to C4086
DM Area
D00000 to D32767
D00000 to D32758
EM Area without bank
E00000 to E32767
E00000 to E32758
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
En_00000 to En_32758
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
Specified values only
#0000
Data Registers
DR0 to DR15
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...