208
Timer and Counter Instructions
Section 3-6
Variations
Applicable Program Areas
Operands
N: Timer Number
The timer number must be between 0000 and 4095 (decimal).
S: Set Value
The set value must be between #0000 and 9999 (BCD).
(If the set value is set to #0000, the Completion Flag will be turned ON when
TIM/TIMX(550) is executed.)
Operand Specifications
Variations
Executed Each Cycle for ON Condition
TIM/TIMX(550)
Executed Once for Upward Differentiation
Not supported.
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
OK
OK
Not allowed
Area
N
S
CIO Area
---
CIO 0000 to CIO 6143
Work Area
---
W000 to W511
Holding Bit Area
---
H000 to H511
Auxiliary Bit Area
---
A000 to A959
Timer Area
0000 to 4095 (decimal)
T0000 to T4095
Counter Area
---
C0000 to C4095
DM Area
---
D00000 to D32767
EM Area without bank
---
E00000 to E32767
EM Area with bank
---
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
---
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to
@ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
---
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_032767
(n = 0 to C)
Constants
---
BCD:
#0000 to 9999 (BCD)
“&” cannot be used.
Binary:
&0 to &65535 (decimal)
#0000 to #FFFF (hex)
Data Registers
---
DR0 to DR15
Index Registers
---
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15